Structural lightweight concrete has an in-place density (unit weight) on the order of 90 to 115 lb./ ft3 (1440 to 1840 kg/m3) compared to normal-weight concrete with a density in the range of 140 to 150 lb./ ft3 (2240 to 2400 kg/m3). For structural applications, the concrete strength should be greater than 2500 psi (17.0 MPa). The concrete mixture is made with a lightweight coarse aggregate. In some cases a portion or the entire fine aggregate may be a lightweight product. Lightweight aggregates used in structural lightweight concrete are typically expanded shale, clay or slate materials that have been fired in a rotary kiln to develop a porous structure. Other products such as air-cooled blast furnace slag are also used. There are other classes of non-structural lightweight concretes with lower density made with other aggregate materials and higher air voids in the cement paste matrix, such as in cellular concrete. These are typically used for their insulation properties. This CIP focuses on structural lightweight concrete.
Lightweight concrete can be manufactured with a combination of fine and coarse lightweight aggregate or coarse lightweight aggregate and normal weight fine aggregate. Complete replacement of normal-weight fine aggregate with a lightweight aggregate will decrease the concrete density by approximately 10 lb./ft3 (160 kg/m3).
Designers recognize that structural lightweight concrete will not typically serve in an oven-dry environment. Therefore, structural design generally relies on an equilibrium density (sometimes referred to as air-dry density); the condition in which some moisture is retained within the lightweight concrete. Equilibrium density is a standardized value intended to represent the approximate density of the in-place concrete when it is in service. Project specifications should indicate the required equilibrium density of the lightweight concrete. Equilibrium density is defined in ASTM C567, and can be calculated from the concrete mixture proportions. Field acceptance is based on measured density of fresh concrete in accordance with ASTM C138. Equilibrium density will be approximately 3 to 8 lb./ ft3 (50 to 130 kg/m3) less than the fresh density and a correlation should be agreed upon prior to delivery of concrete. The tolerance for acceptance on fresh density is typically ±3 lb./ ft3 (±50 kg/m3) from the target value.
Lightweight aggregates must comply with the requirements of ASTM C330. Due to the cellular nature of lightweight aggregate particles, absorption typically is in the range of 5% to 20% by weight of dry aggregate. Lightweight aggregates generally require wetting prior to use to achieve a high degree of saturation. Some concrete producers may not have the capability of pre-wetting lightweight aggregates in cold weather if temperature-controlled storage is not available. Some lightweight aggregate suppliers furnish vacuum-saturated aggregate.
With the exception of bridges and marine structures, specifications for structural lightweight concrete do not typically have a requirement for maximum water-to-cementitious materials (w/cm) ratio. The w/cm ratio of structural lightweight concrete cannot be precisely determined because of the difficulty in determining the absorption of lightweight aggregate.
Air content of structural lightweight concrete must be closely monitored and controlled to ensure that the density requirements are being achieved. Testing for air content must be according to the volumetric method, ASTM C173 or calculated using the gravimetric method described in ASTM C138. Virtually all lightweight concrete is air-entrained.
Finishing lightweight concrete requires proper attention to detail. Excessive amounts of water or excessive slump will cause the lightweight aggregate to segregate from the mortar. Bull floating will generally provide an adequate finish. If the surface for an interior floor is to receive a hard troweled finish, use precautions to minimize the formation of blisters or delamination. See CIPs 13 and 20 for discussions on blisters and delamination, respectively.
Due to the inherent higher total moisture content of lightweight concrete, it typically takes a longer time than normal-weight concrete to dry to levels that might be considered adequate for application of floor covering materials.
The splitting tensile strength of lightweight concrete is used in structural design criteria. The design engineer may request the information for a particular source of lightweight aggregate prior to the design. The splitting tensile strength corresponding to the specified compressive strength is determined in laboratory evaluations. Splitting tensile strength testing is not used as a basis for field acceptance of concrete.
Ensure that the requirements of the designer relative to fire resistance or insulation properties of lightweight concrete building elements are in conformance with applicable industry standards. For a successful project, information is available from the supplier of lightweight aggregate and the ready mixed concrete producer. With proper planning, structural lightweight concrete can provide an economical solution to many engineering applications.