Vapor retarders are frequently specified for interior concrete slabs on grade where moisture protection is desired. Protection from moisture is required when floors will be covered with carpet, tile, wood, resilient, and seamless polymeric flooring, or when moisture-sensitive equipment or products will be placed on the floor. Permeation of water vapor through concrete slabs can cause failure of moisture-sensitive adhesives or coatings, resulting in delamination, distortion or discoloration of flooring products, trip-and-fall hazards, and possibly fungal growth and odors.
Low-permeability membranes below floor slabs on grade, in conjunction with sealed joints, also provide a barrier to radon penetration into enclosed spaces when such conditions exist.
Current recommendation of ACI Committee 302 is to place a concrete slab directly on top of a vapor retarder when the concrete slab surface will receive a vapor sensitive floor covering. If environmental conditions exist for increased possibility of plastic shrinkage cracking, placing concrete directly on the vapor retarder can help alleviate the plastic shrinkage cracking somewhat by enhancing bleed water.
Placing concrete directly on the vapor retarder can also create potential problems. If environmental conditions do not permit rapid drying of bleed water from the slab surface then the excess bleeding can delay finishing operations. Bleed water trapped below a finished surface can cause delaminations (CIP 20) or blisters (CIP 13) if finishing operations are not performed at the correct time after bleed water has disappeared from the surface. Concrete may stiffen slower, which means that trowel finishing operations must be delayed; thus increasing the susceptibility of plastic shrinkage cracking. Curling (CIP 19) can occur due to differential drying and related shrinkage at different levels in the slab. Most of these problems can be alleviated by using a concrete with a low water content, moderate cement factor, and well-graded aggregate with the largest possible size. With the increased occurrence of moisture-related floor covering failures, minor cracking of floors placed on a vapor retarder and other problems discussed here are considered a more acceptable risk than failure of floor coverings.
The sub-grade and base should be adequately compacted.
The base should be well draining and stable to support construction traffic. A clean fine-graded, preferably crushed, material with about 10 to 30 percent passing the No. 100 [150 mm] sieve and free of clay or organic material is generally recommended. Concrete sand should not be used as it is easily displaced during construction.
If recommended in the geotechnical evaluation of the jobsite, install a 6 to 8 inch [150 to 200 mm] layer of coarse gravel or crushed stone as a capillary break. Note that a coarse stone capillary break will not reduce moisture vapor transmission from the subgrade. A vapor retarder is still required above a capillary break.
If a capillary break layer of coarse stone is used, choke the top surface with 2-in. of graded, fine-grained compactable fill to prevent damage to the vapor retarder from sharp corners of the coarse stone. Place the vapor retarder on top of the smooth, compacted fill.
Vapor retarder sheets should be overlapped by 6 inches [150 mm] at the seams and taped and sealed around utility or column openings, grade beams, footings, and foundation walls.
If an interior concrete slab will not have a vapor-sensitive floor covering but will be located in a humidity controlled area it may be placed over the granular fill/blotter layer provided the slab and base material is placed with waterproof roof membrane in place. Further, the granular material should not be subject to future moisture infiltration.
When the choice is made to place the concrete over a granular blotter layer, a minimum 4 inch [100 mm] layer of compactable, easy-to-trim, granular fill material should be used. A “crusher-run” material graded from 1½ in. [37.5 mm] to dust size works well. If this is not practical, cover the vapor retarder with at least 3 inches [75 mm] of crushed stone sand. Do not use concrete sand. To reduce slab friction, top off the crusher-run layer with a layer of fine-graded material. The granular layer should ideally be placed under cover and should be dry prior to concrete placement to function as a blotter and remove water from the fresh concrete.
1. Provide a vapor retarder directly under all interior floor slabs.
2. Place the vapor retarder on a smooth base and ensure it is vapor tight to moisture sources below the slab and at its edges and at penetrations.
3. Order a concrete mixture designed for minimum shrinkage and follow good concrete practices for finishing and curing to reduce potential water vapor emission. If the concrete slab will receive a vapor-sensitive floor covering, cure the concrete under plastic sheeting for 3 days and in no case moist cure the concrete for more than 7 days.